MAXONIC MSC302E-C0CC DISTRIBUTION ISOLATOR

MAXONIC MSC302E-C0CC DISTRIBUTION ISOLATOR

MSC302E DISTRIBUTION ISOLATOR

MODES INPUT SIGNAL 1 INPUT SIGNAL 2 OUTPUT SIGNAL 1 OUTPUT SIGNAL 2
MSC302E-C0C0 4-20mADC NO INPUT 2 4-20mADC NO OUTPUT
MSC302E-C0CC 4-20mADC NO INPUT 2 4-20mADC 4-20mADC
MSC301E-CCCC 4-20mADC 4-20mADC 4-20mADC 4-20mADC

MAXONIC MSC302E-C0CC DISTRIBUTION ISOLATOR

Technical indicators

Working power supply: 24VDC ± 10%

Power consumption: ≤ 1.2W (1 in and 1 out); ≤ 1.8W (1 in and 2 out); ≤ 2.4W (2 in and 2

out)

Input signal:

Power distribution mode, 2-wire system, 4 ~ 20mA

Isolation mode, 4-wire system, 4 ~ 20mA

Distribution voltage: distribution mode, 19 ~ 26V

Distribution protection: maximum short-circuit current, 40mA; Maximum open circuit voltage,

26V

Input impedance: isolation mode, ≤ 200 Ω

Output signal: 4-wire system, 4 ~ 20mA

Output load: 0 ~ 350 Ω

Conversion accuracy: ± 0.1% F.S

Temperature drift: ± 0.01% F.S / ℃

Insulation strength: input / output, ≥ 2000vac (1min); Input / power supply, ≥ 2000vac

(1min); Output / power supply, ≥ 1000VAC (1min)

Insulation resistance: input / output / power=

Feedback